Lorem Ipsum is simply dummy text of the printing and typesetting industry. Lorem Ipsum has been the industry’s standard dummy text ever since the 1500s, when an unknown printer took a galley of type and scrambled it to make a type specimen book. It has survived not only five centuries, but also the leap into electronic typesetting, remaining essentially unchanged. It was popularised in the 1960s with the release of Letraset sheets containing Lorem Ipsum passages, and more recently with desktop publishing software like Aldus PageMaker including versions of Lorem Ipsum.

Specification

Valve:
Static pressure: 1600 kPa / 240 psi
Ambient temperature: -20°C to +50°C / -4°F to +122°F
Media temperature: -20°C to +120°C / -4°F to +248°F
Material:
– Housing: Cast iron ASTM A395, 60-40-18
Valve is uni-directional, hence no flow direction arrow
applies.
– Stem: Stainless steel
– Ball valve: Stainless steel
– Seals, stem: EPDM O-rings
– Seals, ball: Teflon seals
Rotation: 0°-90°
Maximum close-off pressure: 500 kPa / 70 psi
Shut-off leakage: ANSI / FCI 70-2 2006, Class IV / IEC 60534-4, Class IV
End connections: Universal flange connections which can be used with both
ISO and ANSI flanges. Mouting kits are not supplied by Maplef

GENERAL SPECIFICATIONS
ACTUATED CONTROL VALVE – MAPLEF 2 WAY VALVE
1.1. Contractor shall install control valves where indicated in drawings.
1.2. Control valve shall include a universal mounting plate.
1.3. Control valve shall include blow-out proof stem.
2. VALVE ACTUATOR – MAPLEF MT
2.1. Actuator shall be rated to minimum IP22.
2.2. Actuator shall be driven by 24V AC/30V DC or 230V AC, and shall depending on
actuator choice accept 2-10V, 4-20mA, 3-point floating or 2-position control signal.
2.3. Actuator shall have visible indication of position.
2.4. Actuator shall provide minimum torque for full valve shut-off position.
2.5. Optional auxiliary switch versions shall be available on all control types.
2.6. Manual override shall be possible.
3. VALVE HOUSING
3.1. Valve housing shall consist of cast iron ASTM A395, 60-40-18 rated at no less than
1600 kPa (240 psi) at 120°C (+248°C).
3.2. Housing shall be for installation between flanges.
3.3. Valve shall include a ball with laser cut paraolic opening to make flow control equal
percentage; a minimum of 5 unique Kv values shall be available for each size.
3.4. Valve shall withstand a close-off pressure of at least 500 kPa (70 psi).
3.5. Valve ball and ball stem shall consist of stainless steel.
3.6. Indentification tag shall be avilable; tag shall be indelibly marked with Kv, model
number and location; tag shall be aluminum.